Adjusting the impeller pitch angle Rosenberg
The blade angle marking are marked on the blades itself and with increment of 50.
Loosen the fixing screws on the hub/clamp plate to free the impellers.
Rotate the blades and align the new angle marking to the marking on the hub.
Repeat the above step for all the blades.
Re-tighten the hub/clamp plate evenly
Rotate the impeller assembly and check each blades angle again.
Note inAdjusting the impeller pitch angle Rosenberg
One of the fixing screws on the impeller will be longer than the others, and will have
additional balance washers attached. It is VERY IMPORTANT to mark the blades,
hub and clamp plate etc. when disassemble. This is to maintaining existing static
balance of the Impeller.
The contact addresses are to be found in the attachment, or else please phone +49 (0)7940 / 0917 186 894 or email toinfo@rosenberg.com.vn