Description of the controllers / Airtronic Basic for air handling units Rosenberg
Airtronic Basic controllers have been specially designed for the control of Rosenberg housed instruments and they represent optimum comfort and safety in operation, monitoring and service of the system. The most up-to-date DDC technology is used. Amongst the advantages of this technology, the option of customer specific adjustment should be emphasised for very many applications.
Complete operation is carried out remotely via a remote control display on which all fault reports and conditions of the service are shown in writing.
The Airtronic Basic series is manufactured in accordance with VDE (Association of German Electricians)
guidelines. It is available for control of fans with belt drive by standard motors and fans with direct drive by
controllable external rotor motors.
Freely programmable controller with microprocessor, which allows customers' special requirements to be met
Operator unit with 4-line LCD display for messages in writing, 20 characters each
Suitable for front installation or wall mounting
8 digital message inputs (fault messages)
Can be expanded (e.g. subsequent insertion of a cooling sequence or of heat recycling possible)
Operating voltage 24V AC, max 10 VA
Recyclable housing
Control functions for Airtronic Basic for air handling units Rosenberg
Control
Circulation pumps dependent on load and outside temperature
Control of inlet/outlet air dampers
Smooth start mixed air damper
Mixed air damper control manual/automatic
Preheat function of the hot water air heater
Timer switch program
4 switch times per day can be set: temperature and fan level
Monitoring functions for Airtronic Basic for air handling units Rosenberg
Fire/smoke message
Alarm memory in which the last 10 alarm messages may be queried
Air flow monitoring in the inlet and outlet air
Programmable frost monitoring
Overload of inlet and outlet air fan
Filter monitoring in the inlet and outlet air
Cascade control
Inlet air temperature control
Room/inlet air or outlet/inlet air cascade control
Minimal or maximum limiting of the inlet air temperature
PI controller with 3 sequences: heating, cooling, heat recycling
Heating sequence: hot water heat register
Cooling sequence: water air cooler or cooling machine
Heat recycling sequence: plate heat exchanger, glycol circulation or rotary heat exchanger
Set point control according to the outside temperature
Summer/winter compensation
Fan control
3-step speed control with direct drive (external rotor motor)
Single speed with belt drive
Operation
User-friendly operation with 4-line LCD display
LCD operator console as a remote display
Ventilation functions
Supported heating operation
Supported cooling operation
Night ventilation function
Through ventilation function
Rosenberg service package
Switch box
All control devices are manufactured in accordance with VDE (Association of German Electricians)
guidelines and in accordance with EMV (electromagnetic compatibility) guidelines 89/336 EWG and
low voltage guidelines 73/023 EWG, type of protection IP55, plastic cable sheath plate for simple
electrical installation, completely wired and checked.
DDC compact regulator
Wired and preset in accordance with block circuit diagram (pp.14 - 34), assembled. Sensors, control
Valves and other peripherals are supplied loose with them.
Manufacturing services
Taking down and installing the switch box Main electrical connection (feeding in)
Electrical installation of the externally located distributed devices (e.g. temperature sensors, servomotors)
Connection of the heat/cold register with insertion of the control valves enclosed loose into each closed
loop controlled system, as well as assembly of the servo-motors supplied with them
The contact addresses are to be found in the attachment, or else please phone +49 (0)7940 / 0917 186 894 or email toinfo@rosenberg.com.vn