Block circuit diagram 6 for Fans Rosenberg
Inlet and outlet air device
Hot water pump heating, cold water pump cooling, heat recycling (plate heat exchanger)
Switch box, options:
- Inlet air temperature control
- Room temperature control
- Outlet air temperature control
Application:
Ventilation system for rooms in which the inlet air temperature or the room temperature should be
held constant by heating or cooling the inlet air.
The room sensor is placed in the outlet air if no representative measurement value can be located in
the room.
Function:
The temperature measured by the inlet air sensor B1, the room sensor B2 or the outlet air sensor B3 is
compared by the control with the adjusted set point.
In the event of a deviation the controller displaces of the bypass damper. If this is insufficient, the heating
or cooling valve will also be displaced.
Block circuit diagram 7 For Fans Rosenberg
Inlet and outlet air device
Hot water pump heating, heat recycling (circulation loop system (KVS))
Switch box, options:
- Inlet air temperature control
- Room temperature control
- Outlet air temperature control
Application:
Ventilation system for rooms in which the inlet air temperature or the room temperature should be
held constant by heating or cooling the inlet air.
The room sensor is placed in the outlet air when no representative measurement value can be located in
the room.
Function:
The temperatures measured by the inlet air sensor B1, the room sensor B2 or the outlet air sensor B3 is
compared by the control with the adjusted set point.
In the event of a deviation, the controller first displaces the KVS valve. If this is in sufficient to achieve
the desired temperature, the heating valve is opened n addition.