Dismantling procedure of Axial and Bifurcated fans Rosenberg
Place the fan in horizontal position.
Remove the bolt, locking washer and keeper plate from the motor shaft.
Remove the HEX nuts (2 numbers) from the impeller bush.
Use one of the hex nuts and tighten it to the center hole of the bush. This will
separate the impeller from the motor shaft.
Remove the impeller and hub assembly off the motor shaft
Remove the bolts and nuts (4 numbers) from the motor base
Remove motor from the fan case (Motor compartment)
Re-assembling of Axial and Bifurcated fans in Dismantling procedure of Axial and Bifurcated fans Rosenberg
Position the motor in its compartment
Slightly tighten with its bolts and nuts (4 numbers)
Fit the impeller and hub assembly on to the motor’s shaft
Insert the shaft key in its correct position
Tighten the impeller and hub assembly with its HEX nuts
Refit the bolt, locking washer plate into the motor shaft
Relocated the motor centrally to ensure each impeller tip and the inside face of the
fan case has a gap clearance (approximately. 3 to 8mm depending upon diameter)
Tighten the bolts and nuts on the motor’s base
Spin the impeller by hand to confirm free rotation
Check once again to ensure all the bolts and nuts are fully tighten
Note:
Alignment is not required as the impeller assembly is directed to the motor shaft
Always replace motor bearings if the fan is dismantle
The contact addresses are to be found in the attachment, or else please phone +49 (0)7940 / 0917 186 894 or email toinfo@rosenberg.com.vn