Impeller in Product Code Identification for Axial Rosenberg fans
Fluid Flow Rules Of Operation For Fans
Speed variation at constant fan size and constant density :
The volume flow changes proportional to speed All pressures (static, dynamic and total) change square
of the speed
The power requirement changes cube to the speed
Changes in the density at constant speed (or change of the kelvin temperature at a constant flow medium):
The volume flow is not affected
All pressures change proportionately to the density *
The power requirement changes proportionately to the
Density
In the case of changes in the wheel diameter of geometrically similar wheels at constant speed:
The volume flow changes cube to the wheel diameter
All pressures (static, dynamic and total) change proportion to the square of the wheel diameter.
The power requirement changes proportionately to the fifth power of the wheel diameter
V1 / V2 = n1 / n2
p1/ p2 = ( n1 / n2 )2 = ( V1 / V2)2
p1/ p2 = ( n1 / n2 )3 = ( V1 / V2)3
V = const.
p1/ p2 = α1 / α2 = T2 / T1
P1/ P2 = α1 / α2 = T2 / T1
* T1 = To + t1 = 273.15 K + t1
T2 = To + t2 = 273.15 K + t2
V1/ V2 = ( D1 / D2 )3
p1/ p2 = ( D1 / D2)2
P1/ P2 = ( D1 / D2)5
The contact addresses are to be found in the attachment, or else please phone +49 (0)7940 / 0917 186 894 or email toinfo@rosenberg.com.vn