TR devices for controllers Rosenberg Fans

Description of the controller/TR devices

The Rosenberg Compact controller series MSD...TR (for standard motors) or RTE/D...TR (for external rotor motors) is especially suitable for the control of room temperature or inlet air temperature in technical ventilation systems.

The control circuit board contained in the compact untroller series is to set the room or inlet air temperature in conjunction with a room sensor and intake air sensor.

The control takes place on a water heat register by the continuous control of the three-way mixing valve. If on the other hand an electric heat register is used, this is controlled at up to four levels by the module controller i.e. the temperature is controlled by switching on and off the individual heating levels.

If two temperature sensors are connected to the control circuit board, the temperature indication can be

switched between the two actual temperature values.

Adjustments to the closed loop controlled systems can be made at the module controller.

Every piece of equipment has a motor protection device.

This guarantees optimum motor protection for motors with thermocontacts or PTC resistor. If the

maximum permissible coil temperature is exceeded, the motor will be disconnected from the mains supply. After the removal of the cause of the fault and with the voltage restored after disconnection from the mains, the control device can only be switched on again if the system is reset.

The equipment contains a master switch so that the entire system can be switched on.

Programmable controller with microprocessor

Operator unit with three displayed places, decimal point and automatic mathematical signs, 4 operator keys

IP 65 with front installation

1 digital input (used for frost protection)

Operating voltage 12/24 VAC 10% 50/60 Hz, Output 3VA

Key to types of controllers external for rotor motors

Key to types of controllers external for standard motors

Control functions in TR devices for controllers Rosenberg Fans

Temperature control

Control of the heating pump by use of a hot water unit

Control of the cooling pump by use of a cold water unit

Control of inlet and outlet air dampers

Manual continuous control of the mixed air damper

Inlet/outlet air dampers shut on frost alarm

Three-way valve on frost alarm to maximum flow (heating pump on/fan off)

Cascade control

Inlet air temperature control

Room/inlet air or outlet air/intake air cascade control

Minimal limiting of the inlet air temperature

Heating sequence: hot water heat register or electric

air heater (up to 4 levels)

Cooling sequence: water air cooler or cooling

Machine

Timer switch (optional): with weekly/annual program can be set: ON/OFF

Monitoring functions in TR devices for controllers Rosenberg Fans

Overload of inlet and outlet fan

Filter monitoring in the inlet and outlet air

Frost alarm

Overload/overheating monitoring when operating with electric air heater

Fire message input for switching open the fire protection damper or fire and smoke detector

Fan control

In the use of RTE/RTD..TR equipment - 5-step speed control with direct drive

In the use of MSD..TR equipment - 1/2/3 step speed control

Operation

User-friendly operation with written display.

Rosenberg – service package

Switch box

All control devices are manufactured in accordance with VDE

(Association of German Electricians) guidelines and meet EMV (electromagnetic compatibility) guidelines 89/336 EWG and low voltage guidelines 73/023 EWG, type of protection IP55, plastic cable sheath plate for simple electrical installation, completely wired and checked.

Control circuit board

Preset, sensors, control valves and other peripherals are delivered loose with it.

In manufacture

Services in manufacturing

Taking down and installing the switch box

Electrical master connection (feeding in)

Electrical installation of the externally located distributed devices (e.g. temperature sensors, serwmotors)

Connection of the heat/cold register with the insertion of control valves enclosed loose in each closed loop controlled system, as well as assembly of the serwmotors delivered with them

The contact addresses are to be found in the attachment, or else please phone +49 (0)7940 / 0917 186 894 or email toinfo@rosenberg.com.vn