Valve for fans Rosenberg

Servo-motor HAME 15 for control valve for fans Rosenberg

The HAME 15 servo motor is used for the HVRG 3-way valves series. It converts feed.

voltage: 24 V AC 50 Hz

Power consumption: 4 VA

Control: 0 - 10 V

Temp. range: - 10 - +50 °C

Nominal power: 500 N

Nominal stroke: 15 mm

Type of protection: IP 54

Ambient temperature: 0 - 55 °C

Type of protection: IP 54

Description: C:\\Users\\HAO\\AppData\\Local\\Microsoft\\Windows\\INetCache\\Content.Word\\New Picture (15).bmp

Three-way valve HVRG3 in nominal widths of DN15 for fans Rosenberg

Used with controller RTE/D..TR, MSD..TR and Airtronic D /Basic

The three-way valve is used as a control valve in heating, ventilation and air conditioning systems. Preferably for the following applications:

Cold water – minimum temperature of 1°C

Hot water – maximum temperature of 120°C

Other media (on request)

Nominal pressure: PN 16

Nominal size: DN 15 ... DN 50

Flow characteristic: same percentage (log) kvs/Kvo = 30 (VDI/VDE 2173)

Mixing characteristic: linear

Temperature range: 1 ... 120 °C

Leakage losses: Direction of flow 0.1% Kvs

Mixing direction 1% Kvs max. operating pressure: 160 kPa (16 bar)

Nominal stroke: 15 mm

Type of protection: IP 54

Ambient temperature: 0 - 55 °C

Type of protection: IP 54

Description: C:\\Users\\HAO\\AppData\\Local\\Microsoft\\Windows\\INetCache\\Content.Word\\New Picture (16).bmp

Set of nuts for three-way valve HVRG3 for fans Rosenberg

The set of nuts consists of 3 specific nuts for a valve.

Description: C:\\Users\\HAO\\AppData\\Local\\Microsoft\\Windows\\INetCache\\Content.Word\\New Picture (17).bmp