Servo-motor HAME 15 for control valve for fans Rosenberg
The HAME 15 servo motor is used for the HVRG 3-way valves series. It converts feed.
voltage: 24 V AC 50 Hz
Power consumption: 4 VA
Control: 0 - 10 V
Temp. range: - 10 - +50 °C
Nominal power: 500 N
Nominal stroke: 15 mm
Type of protection: IP 54
Ambient temperature: 0 - 55 °C
Type of protection: IP 54
Three-way valve HVRG3 in nominal widths of DN15 for fans Rosenberg
Used with controller RTE/D..TR, MSD..TR and Airtronic D /Basic
The three-way valve is used as a control valve in heating, ventilation and air conditioning systems. Preferably for the following applications:
Cold water – minimum temperature of 1°C
Hot water – maximum temperature of 120°C
Other media (on request)
Nominal pressure: PN 16
Nominal size: DN 15 ... DN 50
Flow characteristic: same percentage (log) kvs/Kvo = 30 (VDI/VDE 2173)
Mixing characteristic: linear
Temperature range: 1 ... 120 °C
Leakage losses: Direction of flow 0.1% Kvs
Mixing direction 1% Kvs max. operating pressure: 160 kPa (16 bar)
Nominal stroke: 15 mm
Type of protection: IP 54
Ambient temperature: 0 - 55 °C
Type of protection: IP 54
Set of nuts for three-way valve HVRG3 for fans Rosenberg
The set of nuts consists of 3 specific nuts for a valve.
The contact addresses are to be found in the attachment, or else please phone +49 (0)7940 / 0917 186 894 or email to info@rosenberg.com.vn